Essential maintenance and fire-prevention procedures for gensets
17 March 2017
Essential maintenance and fire-prevention procedures for gensets

Generating sets (gensets) supply off-grid electricity during power outages, based on diesel or petrol as a fuel source. However, such critical equipment is often neglected. Here ASP Fire provides essential advice on preventative maintenance and adequate fire-prevention procedures for gensets.

The first issue to be taken into consideration is the fuel supply, which may comprise an integral tank at the base of the genset, a 2,200 litre Bulk To Farm Tank (BTF), or often merely a 210 litre drum. “Hence we have the presence of highly flammable liquids, especially in terms of refuelling and the possibility of any spillages,” Michael van Niekerk, CEO, ASP Fire, points out.

Another issue is to control the growth of vegetation around a genset, especially if it is located outside. “Very often we will see vegetation encroaching on a genset, tucked away somewhere as an afterthought. We have even seen corporate customers piling office equipment onto, and around, a genset,” van Niekerk reveals.

He highlights that people also need to be aware that the genset itself is a potential source of fire ignition, due to the high temperatures of the manifold itself. If the genset is located internally, these temperatures can be considerable, especially in the absence of adequate ventilation.

Another important issue is the necessity of proper maintenance. If an oil filter has not been screwed on tightly enough, for example, it can result in an oil leak. “If oil sprays onto a hot manifold as a result of this, a fire will erupt,” van Niekerk warns. Thereafter the temperature will build quickly to a point where entrance into such a room is well-nigh impossible.

Companies and individuals often lack the correct fire-fighting equipment to deal with genset fires. For example, a dry-chemical fire extinguisher will douse the flames, but not cool down any hot surfaces. A carbon-dioxide fire extinguisher, on the other hand, might cool down the overheated genset itself, but this can result in major damage to the equipment due to thermal shock.

Gensets do not only supply standby power, but are essential to the day-to-day operations of institutions such as financial services and medical care. Hospitals, for example, will often have back-up gensets, all located in the same room. If a fire breaks out in one genset, the rest of the equipment is immediately at risk.

“Hence we recommend an automatic fire-suppression system for such environments. It is unmonitored equipment, with a high fire hazard due to the presence of both flammable liquids and combustible products, as well as electricity. The probability of something going wrong may be slim in the mind of the end user, but in the likelihood that it does, the consequences can be potentially disastrous, and even fatal.”

In terms of fixed fire-suppression systems, a range of options are available. Sprinklers are an obvious choice, but this depends on whether or not such a system has been installed already. If not, the cost can be prohibitive, as sufficient hydraulic capacity has to be guaranteed, which means that cheaper and more effective alternatives need to be investigated.

The next best option is a clean-gas fire-suppression system. “The problem with gensets and the heat they produce is that the rooms they are located in are normally ventilated, which compromises the integrity of the enclosure. If you discharge a gas system in this environment, it is therefore not possible to maintain the concentration of that gas for a sufficient period to suppress the fire. This means that clean-gas systems are not ideal in these scenarios,” van Niekerk cautions.

The third option is a water-mist fire-suppression system, which has the added environmental benefit of only using a minimal quantity of water, which is also far more cost-effective than the clean gases themselves necessary to recharge the system.

“This supresses a fire rapidly, cooling any remaining hot spots down to below the automatic ignition temperature.” This is why ASP Fire recommends AFFF water-mist fire-suppression systems for gensets. A foamless system can even be supplied for environments such as gensets housed in shipping containers.

In terms of the total-solutions approach offered by ASP Fire, the company visits a potential client in order to conduct a thorough risk analysis, which includes ascertaining the potential impact on productivity or the bottom line in the event of any genset fire.

“What is your business risk if a genset goes down? Here you are not only looking at protecting the value of your assets, but what does this genset actually support and protect? If it is a hospital or a financial services provider, the implications speak for themselves,” van Niekerk adds.

In these instances, ASP Fire recommends an electronic fire-detection system in conjunction with an AFFF water-mist fire-suppression system. “This allows the end user to monitor the system in terms of any feedback when it is activated in the event of a fire. It is important to bear in mind that all of these systems need to be inspected and serviced at least on a quarterly basis,” van Niekerk points out.

A standalone water-mist fire-suppression system with mechanical activation should be inspected monthly. Gensets should by rights be started up frequently, at least once a week, to ensure the batteries are charged adequately. A cursory visual inspection will also reveal any potential problems or issues.

“It is all about risk mitigation at the end of the day, and how integral the genset is to the business in question. While it is essential for financial service providers and hospitals to invest in the best systems possible, smaller end users also need to look at the impact of genset failure or fire on their businesses. These smaller companies often do not take into account the knock-on effect of a genset going down. Will your business be able to continue operating in such an eventuality?” van Niekerk questions.

In terms of regulations and specifications related to gensets, such enclosures are classified as D4, which implies certain minimum fire-proof requirements, including a specific fire rating for the walls. “If the gensets in a building are not located in a purpose-built room, and are stuck away in the basement, for example, that is a clear violation of the regulations. This is important for end users to bear in mind as well,” van Niekerk concludes.

Archive
News ArticleView Article
Band-It centre-punch clamps for mining, plumbing applications View
EM introduces latest Italian electrical connection systems into SA View
I-CAT is at the forefront of fire-protection innovation for mining View
Automotive industry to phase out environmentally-unfriendly refrigerants View
Bearings International appoints new Financial Director View
Skyriders completes cyclone inspection at Syama Gold Mine in Mali View
Fire detection and prevention in server rooms View
Creating a virtuous cycle for mining View
EM continues to supply the best products at the right price View
Two Crane Giants Join Forces View
12345678910...
Our Partners
ArriveAlive ALCO-Safe
Moolmans PSA
 HSE Solutions
Ctrack Intelligent Solutions Breathalysers
Become a Partner Become a Partner
Links
Quick Links
News
  • Band-It centre-punch clamps for min
  • EM introduces latest Italian electr
  • I-CAT is at the forefront of fire-p
  • Automotive industry to phase out en
  • Bearings International appoints new
  • Skyriders completes cyclone inspect
  • Fire detection and prevention in se
  • Creating a virtuous cycle for minin
  • EM continues to supply the best pro
  • Two Crane Giants Join Forces
  •        Articles
  • Recognize the importance of medical
  • Behavioural implications of alcohol
  • Johnson Controls launches P2000 X-R
  • Improving productivity in the minin
  • Digital Radio to improve mine safet
  • Breathalyser Testing with Lifeloc Q
  • Drug abuse in the workplace – a gro
  • Reporting Unsafe Conditions at Mine
  • Alco-Safe, Breathalysers and Safety
  • Mining regulations on Lifting Machi
  •        Mining Laws
  • Training
  • Downloads
  • Blog
  • About Us
  • Contact Us
  • Home  |   Contact  |   Browser  |   Disclaimer  |   Privacy Policy  |   CMS    
    © 2017 Mining Safety